TON vs RTO: when does a retentive timer matter?

0 replies · 5 views

  1. Controls Trainer Staff

    In Allen-Bradley terms:

    TON (timer on delay) times while the rung is true. The moment the rung goes false, the accumulated time resets to zero.

    RTO (retentive timer on) times while the rung is true, but keeps its accumulated time when the rung goes false. It only goes back to zero when a RES instruction resets it.

    Where RTO earns its place:
    - Counting a motor's total run hours for a PM reminder
    - A lube or filter interval that should count only machine run time
    - A process step that has to total a set time even if it gets paused

    Where it bites people: forgetting the RES, so the timer is already done the next time around.

    What do you use retentive timers for?