Twelve short, animated lessons that make controls easier to understand. Follow the signal, watch the circuit change, then take the next step in the simulator.

Choose a concept.

12 lessons

01

MOTOR CONTROL 26 SEC

Holding, Latching and Seal-In Circuit

See how an auxiliary contact holds the contactor on after you release Start, and how Stop opens the circuit.

Follow the full tutorial
Read transcript

This is a holding circuit, also called a latching or seal-in circuit. Press Start. The contactor energizes, closing its auxiliary contact. Release Start. Current continues through that holding contact, keeping the coil energized. Press Stop. The circuit opens, the contactor drops out, and the motor stops. Practice motor control at controlstrainer.com.

02

MOTOR CONTROL 22 SEC

Why Stop Is Normally Closed

Follow the coil circuit as Stop opens, then see what happens when a wire in that series path breaks.

Follow the full tutorial
Read transcript

Why is Stop normally closed? In this conventional control circuit, a released Stop button completes the path to the coil. Press Stop and the contact opens. Break a wire in that series path and the coil also drops out. That is different from energy isolation. Practice motor control at Controls Trainer dot com.

03

PLC LOGIC 26 SEC

XIC and XIO Test Bits

Compare field-contact position with PLC bit state, then watch XIC and XIO evaluate the same input.

Follow the full tutorial
Read transcript

A normally closed switch does not automatically mean an XIO instruction. These instructions test bits. XIC is true when the bit is one. XIO is true when it is zero. Watch this healthy Stop input: the closed field contact gives a one, so XIC passes. Read the bit, then choose the instruction. Learn PLC logic at Controls Trainer dot com.

04

PLC TIMERS 22 SEC

How a TON Timer Works

Watch a three-second on-delay timer accumulate, set its done bit, and reset when the rung goes false.

Follow the full tutorial
Read transcript

This is a non-retentive on-delay timer. Make the rung true and the accumulated time starts increasing. When it reaches the three-second preset, the done bit turns on. Make the rung false and the accumulated value and done bit reset. The next start begins at zero. Practice ladder logic at Controls Trainer dot com.

05

PLC COUNTERS 25 SEC

One Box, One Count

See why one blocked sensor produces one count, and why a new false-to-true transition matters.

Follow the full tutorial
Read transcript

Why does a PLC counter not count the same box over and over? A count-up instruction counts a false-to-true transition. One box blocks the sensor: one count. Keeping that sensor on adds nothing. The next box produces another rising edge. The accumulated count stays until a reset clears it. Practice PLC logic at Controls Trainer dot com.

06

TROUBLESHOOTING 26 SEC

Command Is Not Feedback

Compare a run command with contactor feedback. A requested action and a confirmed action are different signals.

Follow the full tutorial
Read transcript

The PLC output is on. Does that prove the motor started? No. The command asks the contactor to operate. Auxiliary feedback confirms the contactor responded. Here the command is on, but the feedback is missing. That difference is a clue, not a diagnosis. Compare the command, coil circuit, and feedback. Practice troubleshooting at Controls Trainer dot com.

07

PLC LOGIC 26 SEC

Series AND, Parallel OR

Follow two permissives in series, then compare parallel branches that provide alternative logic paths.

Follow the full tutorial
Read transcript

Series and parallel branches solve different PLC problems. Conditions in series act like AND: both must be true. Parallel branches act like OR: either path can pass. Now put the Stop permission after the branches. It must stay true whichever start path you use. Trace the complete rung, not just one branch. Practice ladder logic at Controls Trainer dot com.

08

ANALOG SIGNALS 27 SEC

Why 4 mA Is Not a Lost Signal

Watch a 4–20 mA process signal and understand why a valid zero reading differs from a lost signal.

Explore the simulator
Read transcript

Four milliamps does not mean zero signal. In this four-to-twenty milliamp example, four represents zero percent, twelve represents fifty percent, and twenty represents one hundred percent. Scaling converts that signal into a useful process value. A reading near zero milliamps can indicate a loop problem, not simply an empty tank. Practice analog controls at Controls Trainer dot com.

09

VFD COMMISSIONING 26 SEC

Program the Motor Rating

Compare the drive rating with the motor nameplate and identify the data used to commission the motor.

Follow the full tutorial
Read transcript

Which current rating belongs in the drive's motor settings? The motor's, not the drive's. Use the motor nameplate for rated voltage, current, frequency, and speed. Then match each value to the correct parameter. A larger drive rating does not change the motor's rating. Follow the drive manual for commissioning. Practice VFD setup at Controls Trainer dot com.

10

VFD CONTROL 25 SEC

Frequency, Speed and Slip

Connect frequency, rotating-field speed and rotor speed in an induction motor, including slip.

Follow the full tutorial
Read transcript

What changes motor speed on a VFD? The drive changes its output frequency. For this four-pole induction motor, thirty hertz gives a synchronous speed of nine hundred RPM; sixty gives eighteen hundred. The running rotor turns a little slower under load because of slip. Actual settings still depend on the motor and machine. Explore VFD control at Controls Trainer dot com.

11

HMI ALARMS 24 SEC

Acknowledge Does Not Fix a Fault

Follow an HMI alarm through acknowledgement and fault clearance, and see why they are separate actions.

Follow the full tutorial
Read transcript

Acknowledging an alarm does not fix the fault. It tells the HMI the operator has seen it. Watch: acknowledge changes the alarm's status, while the fault remains active. Correct the cause and follow the machine's reset procedure. Acknowledge, reset, and start are different actions. Practice HMI controls at Controls Trainer dot com.

12

SAFETY CONCEPTS 28 SEC

Emergency Stop Is Not Isolation

See why stopping motion does not isolate electricity or release stored energy.

Follow the full tutorial
Read transcript

An emergency stop is not an energy-isolating device. It can stop motion while hazardous electrical or stored energy remains. OSHA nineteen ten, one forty-seven distinguishes control-circuit devices from energy isolation. Servicing requires the applicable energy-control procedure: isolate, secure, control stored energy, and verify. Practice these concepts in simulation at Controls Trainer dot com.