Live-dead-live: why you test your meter twice
0 replies · 2 views
-
When you're proving a circuit is dead, the reading only means something if the meter works.
The routine:
1. Check the meter on a known live source.
2. Test the circuit you locked out, every phase to phase and phase to ground.
3. Check the meter on the known live source again.If you skip step 3, you can't rule out the meter dying (blown fuse, dead battery, leads not seated) between steps 1 and 2. A dead meter reads 0 V everywhere.
A proving unit does the same job when there's no handy live source. This is what NFPA 70E means by verifying the absence of voltage.
How does your site handle it? Proving unit, or known source?