Motor trips the overload after a few minutes. Where do you start?

0 replies · 4 views

  1. Controls Trainer Staff

    Classic call. Our usual order:

    • Check the overload setting against the motor nameplate FLA, and the service factor. Make sure someone didn't set it by guessing.
    • Measure the current on all three legs while it runs. One leg much lower or zero is single-phasing.
    • Measure the voltage at the motor, phase to phase. More than a couple of percent imbalance makes a motor run hot.
    • Look at the load: bearings, belt tension, a jam, a gearbox that's going.
    • Heat: a hot enclosure or a motor in direct sun trips sooner.
    • Loose or burnt terminals on the contactor or the overload.

    Remember, taking readings on a running motor is energized work. Wear the PPE the label calls for.

    What's the strangest cause you've found for a nuisance overload trip?

Reply