Motor trips the overload after a few minutes. Where do you start?
0 replies · 4 views
-
Classic call. Our usual order:
- Check the overload setting against the motor nameplate FLA, and the service factor. Make sure someone didn't set it by guessing.
- Measure the current on all three legs while it runs. One leg much lower or zero is single-phasing.
- Measure the voltage at the motor, phase to phase. More than a couple of percent imbalance makes a motor run hot.
- Look at the load: bearings, belt tension, a jam, a gearbox that's going.
- Heat: a hot enclosure or a motor in direct sun trips sooner.
- Loose or burnt terminals on the contactor or the overload.
Remember, taking readings on a running motor is energized work. Wear the PPE the label calls for.
What's the strangest cause you've found for a nuisance overload trip?