Stop button wired NC: why it's XIC in the logic, not XIO
0 replies · 3 views
-
One of the most common questions we get.
A stop button is wired normally closed so that a broken wire stops the machine instead of leaving it running. That means while nobody is touching it, the input is ON (1).
So in the rung you examine it for ON with XIC (examine if closed). When someone presses Stop, the input goes OFF, the XIC goes false, and the rung drops out.
If you use XIO there, the rung is false the whole time the button isn't pressed, and the motor will never start. People then "fix" it by rewiring the button NO, which works until a wire breaks and nobody can stop the machine.
Rule of thumb: in the logic, think about the input's state, not the button's.
Reply
Log in or create a free account to reply. It's free and comes with Levels 1 and 2.