Control transformer: fuse the primary, the secondary, or both?

0 replies · 5 views

  1. Controls Trainer Staff

    On a 120 VAC control circuit fed from a control transformer, you'll typically see:

    • Primary fuses, sized for the transformer and its inrush. Time-delay fuses are common.
    • A secondary fuse in the ungrounded leg (X1).
    • X2 bonded to ground, so a ground fault on the control side blows the fuse instead of starting the machine on its own.

    NFPA 79 and the NEC both have rules on control transformer protection, and the right sizes depend on the transformer rating. Go by the transformer maker's fuse chart and the code edition your site follows.

    Seen a panel where X2 wasn't grounded? What happened?