Half-split method: find the fault in fewer readings
0 replies · 5 views
-
When a control circuit is dead and there are ten devices in series between the source and the coil, don't start at one end and walk to the other.
Measure in the middle. If you have voltage there, the problem is past that point. If you don't, it's before it. Then split the remaining half again. Ten devices take about four readings instead of ten.
A few tips:
- Use the print and the wire numbers so you know exactly where the middle is.
- Reference the return side (neutral or 0 V), not ground, for control circuit readings.
- The PLC can be your meter. If inputs show the state of each device in the string, check the I/O first.These are energized readings: qualified people only, right PPE.