Level 2 — Troubleshooting Bench
On a phone? Play the quick 5-step version for practice. The Level 2 certificate is earned here, on the full panel.
Service call CT‑401: the packaging conveyor stopped about 20 minutes ago and won’t restart. Its panel runs on an Allen-Bradley ControlLogix 5590. Read what the controller and the HMI report, check the readings with the simulated Fluke 87V meter, then lock out, verify zero energy and use the meter to find the failed part before you replace it. Readings depend on the circuit state and the two probe locations. Use the readings to trace the fault; verify zero energy before making repairs.
Meter
Control‑panel test points conveyor dead
Laid out like a real panel: power at the top (main disconnect, distribution block, motor fuses, starter M1, transformer fuses and T1); then control power, a dedicated controller rack row, and the terminal strips. The door devices (Start, Stop, E-Stop, fault light) and the field devices (motor, photoeye) are below the dashed line, off the backplate. How this panel is fed: the main disconnect feeds an Allen-Bradley 1492-PD3141 distribution block, which splits its load side between the motor branch and control transformer T1 (1497A-A8-M6-0-N, 350 VA, 480 to 120 V; the H2–H3 link sets the primary for 480 V). T1 is sized so its sealed load — the rack supply (100 VA maximum) plus the 24 V DC supply (at most 192 VA at 120 V) — stays under 350 VA. Its primary fuses F5/F6 are Bussmann FNQ-R-1-8/10 (1.8 A) and its secondary fuse F1 is an FNQ-R-4 (4 A): Rockwell’s table maximums for a 350 VA transformer at 480/120 V with both sides fused (1497-TD001, Tables 13 and 14), not a verified start-up check. Open item: Rockwell publishes the switch-on inrush peaks of the two supplies (1756-PA72: 20 A maximum; 1606-XLP72E: 26–30 A) but no duration, so whether F1, F5/F6 and T1 ride through switch-on is not verified on this drawing. X2 is never fused (NEC 240.22): it lands on white bridged terminals XT and is bonded to the ground bar at one point (XT-3B to PE4). F1 feeds gray bridged terminals X1T, so each supply gets its own conductor. The controller rack has its own supply, an Allen-Bradley 1756-PA72 on 120 V AC; its installation instructions (1756-IN619G) call for a 15 A time-delay fuse in each ungrounded supply conductor, and here that conductor is protected by F1 — reconciling the two is part of the open item. The 24 V DC supply, an Allen-Bradley 1606-XLP72E (listed NEC Class 2), now feeds only the field devices and the I/O: +V runs through fuse F7 (Bussmann LP-CC-4, as on Level 1) to terminal strip TB1; 0 V is TB2, grounded by one bonding jumper (TB2-4B to PE5; the supply’s own PE terminal is not connected to its −V). The motor branch is protected by Class CC time-delay fuses F2-F4, one per phase, between the distribution block and starter M1 (NEC 430.52): each is a Bussmann LP-CC-6 (6 A), about 175% of the 2 hp, 460 V motor’s 3.4 A full-load current (NEC Table 430.250) and under the 300% maximum for time-delay Class CC fuses, in a 1492-FB1C30 holder rated 30 A maximum. Starter M1 is an Allen-Bradley 100-C09EJ10 contactor with a 193-T1AB40 overload relay mounted directly underneath (2.9–4 A, set to the motor nameplate FLA, 3.4 A; Table 430.250 also lists 3.4 A for 2 hp at 460 V: the fuses are sized from the table, the overload from the nameplate) and a front-mounted bifurcated auxiliary block, 100-FCB11, whose contact 23-24 tells the controller that M1 has really pulled in (drawn enlarged in the bottom row). The controller: a ControlLogix 5590 (1756-L902TS, slot 0) in a 1756-A4 chassis with a 1756-IB16 input module (slot 1), a 1756-OB16E output module (slot 2) and a 1756-N2 filler (slot 3). Field wiring lands on the modules’ 1756-TBNH removable terminal blocks, shown directly on their modules in the enlarged rack. The coil string is hardwired: OB16E OUT-0 → E-Stop 11-12 → overload 95-96 → M1 A1. The rack and module pictures are training illustrations, not product photos. The incoming protective (ground) conductor lands on the copper ground bar, which is bolted straight to the backplate (BOND1/BOND2); the backplate is bonded to the enclosure. Every conductor carries its wire number on a sleeve at each end; runs inside the covered wireways are hidden and change ducts only through the vertical ducts. One conductor per terminal. This is a training drawing: always follow the device manufacturers’ terminal ratings and your site’s electrical drawings.
Packaging Conveyor STOPPED
—
Controller program — ControlLogix 5590 · MainRoutine
PLC program, standard task (periodic, 10 ms). Read-only: an instruction lights green while it is true. This is ordinary control logic, not a safety function: the E-Stop contact 11-12 and the overload contact 95-96 stop M1 in hardware, with no controller in the path.
Accuracy & safety basis for this panel — parts and sources, how the controller avoids a restart, open items, simplifications
Equipment and sources
- Controller: Allen-Bradley ControlLogix 5590, 1756-L902TS (Rockwell 1756-TD001: one USB port and two embedded EtherNet/IP ports; 1.20 A at 5.1 V). Only its standard task is used: the 1756-IB16 and 1756-OB16E are standard I/O, not safety I/O, and the program below is not a safety function.
- Rack: 1756-A4 chassis; 1756-PA72 supply (85–265 V AC, input 100 VA maximum, inrush 20 A maximum, hold-up 6 cycles at 120 V: 1756-TD005J p.3; terminals and fusing instruction: 1756-IN619G p.5); 1756-N2 filler in the empty slot (1756-TD006).
- I/O: 1756-IB16, 16 sinking inputs, ON from 10 V; 1756-OB16E, 16 sourcing outputs, 1 A per point, electronically fused per group of 8 (1756-TD002U pp.45 and 102–104; RTB pin assignments read from its wiring drawings). A group fuse trip turns the whole group off and sets FuseBlown bits that stay latched until reset (1756-UM058L p.36 and p.123). Terminal blocks 1756-TBNH. Backplane load 1.20 + 0.10 + 0.25 = 1.55 A at 5.1 V of the PA72’s 10 A.
- Control power: transformer 1497A-A8-M6-0-N, 350 VA; F5/F6 Bussmann FNQ-R-1-8/10 and F1 FNQ-R-4 are the Table 13 and 14 maximums of 1497-TD001 for 350 VA at 480/120 V. 24 V DC supply 1606-XLP72E (Class 2); F7 Bussmann LP-CC-4.
- Motor circuit: contactor 100-C09EJ10 with an electronic 24 V DC coil (closing and opening delays 20–50 ms: Rockwell 100-TD013, Table 19); overload 193-T1AB40; 2 hp, 460 V motor (nameplate FLA 3.4 A; NEC Table 430.250 also lists 3.4 A for 2 hp at 460 V: the fuses are sized from the table, the overload from the nameplate) on the 480 V system.
- Rack grounding: the chassis protective-earth stud (14 AWG) and its functional earth at the leftmost bottom mounting tab (8 AWG) each run to their own bolt on the ground bus (1756-IN621E pp.11–14); the PA72’s PE terminal goes to the ground bus (“Attach to chassis ground lug or ground bus”, 1756-IN619G p.5).
- Terminal blocks: on a real 1756-TBNH the conductors are dressed down to the strain-relief area at its bottom and tied there (1756-IN062F p.6). The enlarged breakouts draw each conductor leaving sideways so that every screw stays visible and probeable.
- Photoeye: Allen-Bradley 42JT-P2LAT1-A2 VisiSight, polarized retroreflective with reflector 92-125, 2 m cable: 10–30 V DC, 30 mA maximum, output 100 mA maximum, off-state leakage 10 µA maximum (42JT-IN002B p.5), well inside the IB16’s 1.5 mA off-state limit. Its black output sources into the IB16 and, at the factory dark-operate setting, is ON while a box blocks the beam (p.2; the p.1 table labels the same behavior “Light Operate”, a wording conflict in the maker’s document). The white remote-teach lead is not connected. The picture is a generic photoeye.
- Fault light: Allen-Bradley 800FP-P4PN3R, a 22 mm red LED pilot light for 24 V AC/DC, 24 mA at 24 V DC, terminals X1/X2 (800-TD008G pp.5 and 9). The OB16E’s 1 mA off-state leakage (1756-TD002U p.104) is below the light’s 3 mA leakage rating, so an off output does not light it.
- Run feedback: M1_Aux comes from a front-mounted bifurcated auxiliary block, Allen-Bradley 100-FCB11 (contacts 23-24 N.O. and 31-32 N.C., for C09 contactors with the integral 13-14), rated for switching down to 5 V / 3 mA (100-TD013Q pp.31 and 47). The contactor’s integral 13-14 is rated only down to 17 V / 10 mA, so it is left spare. Whether the IB16 input always draws at least that 3 mA is an open item (below).
- F7: Bussmann LP-CC-4, Class CC time-delay, 600 V AC / 150 V DC (Bussmann data sheet 1023).
- Pictures: the rack, modules, terminal blocks and E-Stop are training illustrations, not product photos; every probe ring is placed on the picture’s own screw.
How the controller avoids an unexpected restart (each case is tested on this page)
- The E-Stop’s contact 11-12 and the overload’s 95-96 open M1’s coil string in hardware. The program only reports and permits.
- The start permit (rung 7) is granted only while Start and RUN are both released, then holds itself. Stop (door or HMI), the E-Stop, a trip or a fault drops it. So a Start or RUN held through a stop, an E-Stop release, a RESET or power returning never starts M1: it has to be released and pressed again.
- Pickup window, 150 ms (rung 1): if M1’s aux contact has not confirmed within 150 ms of the run command, the start is dropped and a fault latched. If the output supply is missing at the press, or drops while M1 is still closing, and returns inside the window with Start still held, that same start completes late: the motor never ran, so it is a delayed start, not a restart. Past the window, the start is aborted.
- Established run (rungs 2 and 3): once confirmed, any loss of M1_Aux while the run command is on drops the permit in the same scan, with no timer, and latches a fault.
- Output group fuse (rung 4): any group 0 FuseBlown bit drops the permit (all eight bits are tested, because which bits a group trip sets is not documented).
- Latched M1_Fault (rungs 5 and 6): RESET FAULT clears it only once every cause is gone, and RESET never starts M1.
- Power: the rack supply holds the backplane up for 100 ms; a longer loss stops the controller. At power-up the firmware prescan clears the run command and the permit, so Start must be released and pressed again.
Open items (not claimed)
- Switch-on inrush: Rockwell gives the PA72’s 20 A and the XLP72E’s 26–30 A peaks with no duration or I²t, so whether F1 and F5/F6 ride through switch-on, and T1’s voltage during it, are NOT verified. Closing this needs the makers’ inrush duration or I²t, or a measurement on real hardware.
- The PA72 instructions call for a 15 A time-delay fuse in each ungrounded supply conductor; this branch is protected by F1 (4 A time-delay). The two are not reconciled here, and no compliance claim is made.
- Run-feedback contact current: Rockwell publishes the IB16’s on-state current only as 2 mA minimum at 10 V and 10 mA maximum (3.12 kΩ maximum impedance) at 31.2 V (1756-TD002U p.46). Treating the input as a resistor gives about 7.6 mA at 24 V, but that is an estimate, not a verified minimum for the 100-FCB11’s 3 mA rating; it needs Rockwell’s input curve or a measurement.
Why the overload is found the way it is
- A normal overload trip also opens 95-96 and closes 97-98, so those states alone do not prove a failed relay. The lesson asks for its own RESET after it has cooled (it will not latch), a check that the motor circuit is not the cause (balanced line-to-line winding readings), and the open 95-96 shown with the ohmmeter on the de-energized circuit.
- The controller never holds the coil output on without run feedback, so the coil string cannot be traced live. The ohmmeter is used instead, and its readings count only after zero energy has been verified under your own lock and tag.
Simplifications in this simulation
- The program reads its inputs once per 10 ms scan. A real module delivers its data asynchronously, at its RPI, so production code buffers inputs at the start of the routine. An interruption shorter than about one scan plus the input filter may not be seen.
- Controller start-up is shortened to 4 s. The contactor’s minimum OFF time is not modeled.
- Ohmmeter: readings are solved through every parallel path of the de-energized circuit. The transformer windings use typical values (Rockwell publishes none), and the motor uses a typical 10.9 Ω line to line (a comparable 2 hp 460 V motor’s maker data: 10.857 Ω, Baldor-Reliance EM3558T, typical, not guaranteed). Electronic loads (M1’s coil, the pilot light, the supplies and the I/O circuits) are left out and read OL. Rockwell publishes no coil resistance for the 100-C09EJ10’s electronic coil.
- The bimetallic overload’s cooling time is not modeled: the lesson states that the line stopped about 20 minutes before your RESET attempt.
- No fault in this lesson trips the output group fuse; that path is exercised by the page’s tests.
This page is a training simulation. It is not an electrical-safety certification of any real circuit.