Controls Trainer Level 2 — Troubleshooting
My TrainingHome

Level 2 — Troubleshooting Bench

On a phone? Play the quick 5-step version for practice. The Level 2 certificate is earned here, on the full panel.

Service call CT‑401: the packaging conveyor stopped about 20 minutes ago and won’t restart. Its panel runs on an Allen-Bradley ControlLogix 5590. Read what the controller and the HMI report, check the readings with the simulated Fluke 87V meter, then lock out, verify zero energy and use the meter to find the failed part before you replace it. Readings depend on the circuit state and the two probe locations. Use the readings to trace the fault; verify zero energy before making repairs.

FLUKE 87 V TRUE RMS MULTIMETER ⚡ AC DC Auto •))) MIN MAXRANGEHz % REL ΔHOLDAuto AmA µACOMVΩ 10A MAX400mA CAT III 1000VCAT IV 600V

Meter

Function: OFF — leads in COM + VΩ (voltage/resistance).
Click a lead on the meter — red at the VΩ jack or black at COM — to pick it up, then click a terminal on a device to land it.

Control‑panel test points conveyor dead

Swipe sideways to see the whole panel.
Land the leads on any terminal ring, including the enlarged I/O terminal blocks. Energized, read volts; locked out and verified dead, the Ω function finds an open contact.

Laid out like a real panel: power at the top (main disconnect, distribution block, motor fuses, starter M1, transformer fuses and T1); then control power, a dedicated controller rack row, and the terminal strips. The door devices (Start, Stop, E-Stop, fault light) and the field devices (motor, photoeye) are below the dashed line, off the backplate. How this panel is fed: the main disconnect feeds an Allen-Bradley 1492-PD3141 distribution block, which splits its load side between the motor branch and control transformer T1 (1497A-A8-M6-0-N, 350 VA, 480 to 120 V; the H2–H3 link sets the primary for 480 V). T1 is sized so its sealed load — the rack supply (100 VA maximum) plus the 24 V DC supply (at most 192 VA at 120 V) — stays under 350 VA. Its primary fuses F5/F6 are Bussmann FNQ-R-1-8/10 (1.8 A) and its secondary fuse F1 is an FNQ-R-4 (4 A): Rockwell’s table maximums for a 350 VA transformer at 480/120 V with both sides fused (1497-TD001, Tables 13 and 14), not a verified start-up check. Open item: Rockwell publishes the switch-on inrush peaks of the two supplies (1756-PA72: 20 A maximum; 1606-XLP72E: 26–30 A) but no duration, so whether F1, F5/F6 and T1 ride through switch-on is not verified on this drawing. X2 is never fused (NEC 240.22): it lands on white bridged terminals XT and is bonded to the ground bar at one point (XT-3B to PE4). F1 feeds gray bridged terminals X1T, so each supply gets its own conductor. The controller rack has its own supply, an Allen-Bradley 1756-PA72 on 120 V AC; its installation instructions (1756-IN619G) call for a 15 A time-delay fuse in each ungrounded supply conductor, and here that conductor is protected by F1 — reconciling the two is part of the open item. The 24 V DC supply, an Allen-Bradley 1606-XLP72E (listed NEC Class 2), now feeds only the field devices and the I/O: +V runs through fuse F7 (Bussmann LP-CC-4, as on Level 1) to terminal strip TB1; 0 V is TB2, grounded by one bonding jumper (TB2-4B to PE5; the supply’s own PE terminal is not connected to its −V). The motor branch is protected by Class CC time-delay fuses F2-F4, one per phase, between the distribution block and starter M1 (NEC 430.52): each is a Bussmann LP-CC-6 (6 A), about 175% of the 2 hp, 460 V motor’s 3.4 A full-load current (NEC Table 430.250) and under the 300% maximum for time-delay Class CC fuses, in a 1492-FB1C30 holder rated 30 A maximum. Starter M1 is an Allen-Bradley 100-C09EJ10 contactor with a 193-T1AB40 overload relay mounted directly underneath (2.9–4 A, set to the motor nameplate FLA, 3.4 A; Table 430.250 also lists 3.4 A for 2 hp at 460 V: the fuses are sized from the table, the overload from the nameplate) and a front-mounted bifurcated auxiliary block, 100-FCB11, whose contact 23-24 tells the controller that M1 has really pulled in (drawn enlarged in the bottom row). The controller: a ControlLogix 5590 (1756-L902TS, slot 0) in a 1756-A4 chassis with a 1756-IB16 input module (slot 1), a 1756-OB16E output module (slot 2) and a 1756-N2 filler (slot 3). Field wiring lands on the modules’ 1756-TBNH removable terminal blocks, shown directly on their modules in the enlarged rack. The coil string is hardwired: OB16E OUT-0 → E-Stop 11-12 → overload 95-96 → M1 A1. The rack and module pictures are training illustrations, not product photos. The incoming protective (ground) conductor lands on the copper ground bar, which is bolted straight to the backplate (BOND1/BOND2); the backplate is bonded to the enclosure. Every conductor carries its wire number on a sleeve at each end; runs inside the covered wireways are hidden and change ducts only through the vertical ducts. One conductor per terminal. This is a training drawing: always follow the device manufacturers’ terminal ratings and your site’s electrical drawings.

Lockout / Tagout & Repair
Main Disconnect: ON
Lockout station take a hasp take a hasp take a hasp take a lock take a lock take a lock take a lock take a tag take a tag
1
Prove the circuit is de-energized
2
Replace the faulted component
3
Remove LOTO
✔ Conveyor CT-401 restored — replaced under lockout, zero energy verified, line proven running. Service call closed.

Packaging Conveyor STOPPED

packaging conveyor
Motor M1 de-energized — belt will not move.
Diagnose, lock out, replace the faulted part, then prove the line runs.
Allen-BradleyPanelView Plus 7
Packaging Line 3Conveyor CT-401
—
—
▶
RUNConveyor Running
■
STOPReady / Idle
⚠
FAULTActive Fault
—
—
I/O Status
Inputs · Local:1 (1756-IB16)
I.Data.0Start_PB
I.Data.1Stop_PB (NC)
I.Data.2Motor_OL_Trip
I.Data.3M1_Aux
I.Data.4EStop_OK (NC)
I.Data.5Photoeye
Outputs · Local:2 (1756-OB16E)
O.Data.0Motor_Run
O.Data.1Fault_Light
⚠ Alarm Summary
TimeTagMessageState

Controller program — ControlLogix 5590 · MainRoutine

PLC program, standard task (periodic, 10 ms). Read-only: an instruction lights green while it is true. This is ordinary control logic, not a safety function: the E-Stop contact 11-12 and the overload contact 95-96 stop M1 in hardware, with no controller in the path.

    Accuracy & safety basis for this panel — parts and sources, how the controller avoids a restart, open items, simplifications

    Equipment and sources

    How the controller avoids an unexpected restart (each case is tested on this page)

    Open items (not claimed)

    Why the overload is found the way it is

    Simplifications in this simulation

    This page is a training simulation. It is not an electrical-safety certification of any real circuit.